Raritan Branch Circuit Monitor
Data Center Panelboard and Busway Monitoring
- Meters Floor PDU, RPPs, Panelboards, and Busways.
- One controller supports up to 70 power meters.
- Quick configuration via USB stick preloaded with panel schedule.
- CTs connect to live circuits.
- Auto-correct metering adjusts for CT orientation on wires.
- Real-time configurator.
- USB ports for configuration, Wi-Fi networking, and tablet display.
- Supported by DCIM software that offers auto-discovery as a panel.
- Several enclosure options.
- Same firmware as Raritan rack PDUs.
- Remote display using PDView app.
- Collects data on: A, V, kW, kVA, power factor, and kWh.
- Protocols include TCP/IP, Modbus and SNMP.
- Environmental sensor support
Raritan’s intelligent Branch Circuit Monitoring (BCM) system allows you to fully utilize your power infrastructure and manage capacity as your data center grows and changes. Whether you are retrofitting an existing facility, or planning for growth or new construction, Raritan’s BCM system can help you reduce energy costs, track power usage, and prevent downtime. Easily add metering where it never existed before.
This easy-to-deploy modular system, enables real-time views of electrical capacity and power usage on branch circuits, and mains, in an electrical service entrance or a remote power panel. It sends threshold alerts for power and environmental conditions, thereby helping to prevent downtime. The data can also support energy efficiency and customer charge-back initiatives. Plus it integrates with Power IQ® DCIM Monitoring Software, and other building management system (BMS) and DCIM solutions.
This easy-to-deploy modular system, enables real-time views of electrical capacity and power usage on branch circuits, and mains, in an electrical service entrance or a remote power panel. It sends threshold alerts for power and environmental conditions, thereby helping to prevent downtime. The data can also support energy efficiency and customer charge-back initiatives. Plus it integrates with Power IQ® DCIM Monitoring Software, and other building management system (BMS) and DCIM solutions.
Application | Part Number | Description |
Enclosure for monitoring panelboards — suggested for raised floor environments | BCM2-9610Y-KIT-01 | BCM2-9610Y-KIT-01 BCM2-9610Y (Up to 480V, 16A 3PY Terminal, 96 channel branch circuit meter enclosure with controller) BCM2-250A-CT-4PK (4x 250A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-1A-CT (1x 1A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-MCTcable-3M (mains circuit cable for 5x CTs) 2x BCM2-60A-CT-12PK (12x 60A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-BCTcable-3M-1, BCM2-BCTcable-3M-2, BCM2-BCTcable-3M-3, BCM2-BCTcable-3M-4 (branch circuit cables for 12x CTs each) BCM2-FLOOR-MOUNT-KIT |
DIN rail modules for monitoring panelboards | BCM2-DIN-KIT-D01 | PMC-1001 (rack/wall mount power meter controller) PMM-1000 (3Phase, 480V DIN rail power meter module) PMB-1960 (96 port power meter branch) BCM2-250A-CT-3PK (3x250A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-MCTcable-3M (mains circuit cable for 5x CTs) 2x BCM2-60A-CT-12PK (12 x 60A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-BCTcable-3M-1, BCM2-BCTcable-3M-2, BCM2-BCTcable-3M-3, BCM2-BCTcable-3M-4 |
DIN rail modules for monitoring Busway Mains | BUS-DIN-KIT-D01 | PMC-1001 (rack/wall mount power meter controller) PMM-1000 (3Phase, 480V DIN rail power meter module) BCM2-250A-CT-3PK (3x 250A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-MCTcable-0.5FT (mains circuit cable for 5x CTs) BCM2-1A-CT (1x 1A current transformer / 0.5% / 333mV / 24” / 610mm lead) |
Voltage Measurement Inputs
- Input Range*
- 90–277V LN, 156–480V LL
Measurement Category
- CAT III, Pollution Level 2
Frequency
- 50/60 Hz
Current Measurement Inputs
- CT Type
- Voltage Output = 333 mV at rated current
CT Rated Current
- 1–1200A
Power Requirements
- Voltage
- 90–240V
Current
- 0.2A
Environmental
- Operating Temperature
- 0°–60°C (32°-140°F)
Operating Humidity
- 5–85%
Operating Elevation
- 0-3000m
Meter Measurement Accuracy
- Active Power & Energy
- 0.5%: IEC 62053 Class .5, EN 50470-3 Class C
Reactive Power & Energy
- 2%
RMS Voltage & Current
- 0.2%
Frequency
- 0.1%
Sample Rate
- 64x 50 or 60 Hz (phase locked)
Measurement Update Rate
- 3 secs: IEC 61000-4-30 Class S
Conformance
- Safety
- UL/EN 61010-1
EMC/EMI
- EN61326-1, FCC Part 15 Class A
Klanten keken ook naar deze producten