Raritan PX2-1085I2U-O1
Monitored rack power distribution unit
(0U [vertical], 17.3kVA, 48 outlets).
Monitored rack power distribution unit (0U [vertical], 17.3kVA, 48 outlets).
INPUT:
415v (3-phase WYE), 32a - IEC 60309 3P+N+E 6h 32A plug (4P5W);
OUTPUT:
36@ C13
12@ C19
on 6@ 1-pole, 20a Overcurrent Protectors;
FEATURES:
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse;
3-digit LED user-selectable display (voltage, current, or active power : per line or per breaker).
Local display of alarms and configuration information(name, ratings, IP/Networking);
Auto-flip orientation;
(10/100) Ethernet port
Tri-color status LED per receptacle.
Max Dimensions 52mm x 55mm x 1829mm (2.1in x 2.2in x 72.0in).
Max Weight 8 kg
Maximum ambient temperature 60C at full load.
Features
- Energy Metering
Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy
ISO/IEC 62053-21 1%
Remote Outlet Switching
No
Metering per input line
Yes for all models
Metering per Branch Circuit Breaker
Yes
Environmental Sensor Ready
Yes
Compatible Sensors
Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.
Cascading
Yes, Max 16 PDUs can be daisy chained using a USB connection. Note: Firmware version 3.3.10 or above is required.
Networking
10/100/1000 BaseT Ethernet,
Optional WiFi (802.11 a/b/g/n).
Onboard Display
3-digit LED user-selectable display (voltage, current, or active power : per line or per breaker)..
Auto-flip orientation
Specifications
- Input
- Input Plug
IEC 60309 3P+N+E 6h 32A (4P5W)
Nominal Voltage
415V
Maximum Input Current
32A
Rated Input Current
24A
Power Capacity
17.3kVA
Cord Length
3m
Output
- Nominal Voltage
240V
Receptacles (Output Connections)
(36) IEC320 C13
(12) IEC320 C19
Overload Protection
(6) L41-B0-42-620-H22-D3
Physical
- Dimensions (WxDxH)
2.1in x 2.2in x 72.0in; 52mm x 55mm x 1829mm
Unit Weight
8 kg
Shipping Weight
11.5 kg
Shipping Dimensions
365mm x 135mm x 2227mm
Mounting
Tool-less Button Mount
Environmental
- Operating Temperature/Environment
60 C
Operating Relative Humidity
85%
Operating Elevation
0-10000ft
Conformance
- Regulatory Approvals
UL